6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
.2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used.
Paddock drain cover screws are expired and had to have been replaced by Feb 1. EHS observed screws not changed. Operator changed screws and provided health department with documentation. No permit action. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Observed pool chemicals not stored in designated chemical storage room - instead stored in storage room hallway off of pool deck which is not ventilated. |