| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
PH 8.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8.
*Immediate suspension item |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records have out of range pH for multiple days with no maintenance correction or closure. Main drains are missing a screw and main drain being checked. Ensure records are accurate..
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
One main drain missing a screw on the left. .2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
.2537(7) Drain covers shall be in good condition and securely attached.
Checked that drain is secure. Immediate suspension item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Water level to surface of pool.
.2518(k) Water level shall be maintained to assure skimmers are operable. Operator lowered and corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door from front entry and door to patio not latching or alarmed. .2537(b) All gates and doors shall be self-closing, self-latching.
*Permit item |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Underwater light out at time of inspection. Pool operates at night..2524(d) Provide sufficient underwater lighting.
*permit item |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not working at time of inspection. .2518(g) Keep flow meter operational.
*permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed standing water on pump room floor. .2533(d) Pump room floor shall be kept dry and free of standing water.
Light not working in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
Inadequate ventilation in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Inadequate ventilation in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Pool built 2008. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms over 110 F. .2526(i) Water in restrooms shall not exceed 110 F. |