Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHILTON GARDEN INN AYRSLEY
Address1920 AYRSLEY TOWN BLVD
 
City/State/ZIP
CHARLOTTE NC 28273
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 2/21/2023
Final Score @ Grade
8
General CommentsIssued permit for 2022/2023 season. Contrasting color bands have been corrected, spare pump basket provided. Doors self-closing and alarm installed at gym door. No propping doors open. PERMIT RESTRICTION - FLOW METER MUST REMAIN OPERABLE AT 60 GPM DUE TO FLOW RESTRICTION OF THE EQUALIZER LINE AND FILTER. Jandy VSFHP270DV2A, 2.7 THP pump Blue White flow meter installed on 3” pipe with 18” inlet and 32” outlet Flow meter at 60 gpm. All pipes (md, sk, return) 3” (2) Aquastar 9MFxxx 2008 drain covers (2) Aquastar 6HPHAxxx 2008 EQ line covers (1) TR100 filter (5) returns (2) skimmers

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Records missing main drain checks for multiple days. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked, recorded and corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Observed standing water on pump room floor from spa. .2533(d) Pump room floor shall be kept dry and free of standing water.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms over 110 F. No toilet paper in women’s restroom. .2526(i) Water in restrooms shall not exceed 110 F. .2526(l) Provide toilet paper and dispensers in restrooms.