2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(5) Maintain bromine at least 2.0 ppm. Observed bromine level of 0.0ppm at time of inspection. IMMEDIATE SUSPENSION ITEM. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH level of 8.4 at time of inspection. CDI: CPO corrected pH level. Pool now reads 7.7. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Observed walls at water line stained with gray film. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Surface skimmers shall be installed per manufacturer's instructions. Observed weir on deep end of pool not attached securely. MAY WARRANT INTENT TO SUSPEND. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed cover for vacuum port with no cover and beginning to separate from wall. MAY WARRANT INTENT TO SUSPEND. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed standing water on pump room floor. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(i) Water in restrooms shall not exceed 110 F. Observed hot water in men's restroom at 129F and women's restroom at 114F. |