Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHOMEWOOD SUITES
Address125 HARBOUR PLACE DR
 
City/State/ZIP
DAVIDSON NC 28036
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 11/18/2019
Final Score @ Grade
24
General CommentsPermit not posted in the pool area. Go to Meckpools.Charmeck.org to print a copy of the permit to post in the pool area. Cyanuric Acid tested at 90 ppm. The maximum allowable is 100 ppm. Recommend partially draining and refilling to reduce the Cyanuric Acid level. Operator getting very different readings with strips than I am with my Taylor test. Recommend using a more accurate and precise test kit. Immediate suspension issued. 2) 3) Contact Will Harrison (704-507-6824) for reinspection when issues have been corrected.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No No free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. Operator able to adjust to 0.1 ppm. - Immediate suspension item.
3 6 Water quality: pool water pH No No No pH < 6.8. .2535(1) Maintain pH at 7.2 to 7.8. Operator added over a scoop, still less than 6.8. - Immediate suspension item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No One weir installed upside down. .2518(k) Surface skimmers shall be installed per manufacturer's instructions. - Corrected by operator.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladder missing endcap, digging into the side of the swimming pool. .2521 Install ladders per manufacturer instructions. Handrail only attached at one end, other end free floating. .2521(b) Handrails, if removable, shall be installed in such a way than they cannot be removed without the use of tools. Corrected by operator.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter stuck. .2518(g) Keep flow meter operational. - Corrected by operator.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chemical storage room packed full of general storage items. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.