Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form indicated Pentair CHII-NI-3/4FE pump, pump is Pentair Callenger CHII-N1-1FE (P/N 345205). Only motor had been changed at last inspection and pool has been closed. Pump was changed back to original since last inspection.
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
Verified pump curve and no suction hazard in field. Allowing CPO to submit updated PDSC form with pump change within 1 week, by 6/25 or permit action will be taken. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items and storage within 3’ of equipment and piping. Fan not operating in chemical storage.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |