Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Test kit missing alkalinity test and missing on records. .2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*30 Day Intent to Suspend item |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Skimmer equalizer line is plugged in skimmer, but cover on wall is plastered over. PDSC form indicates plugged per State recommendations, which means the hole should be plastered over at wall or plugged. Old cover should be removed from pool wall. Allowing 30 Days for correction since there is not a suction hazard, but needs correction. .2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
*Permit item |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed one ladder rung not connected on left side. This is imposing a hazard, issuing 30 Day Intent to Suspend*
.2521 Install ladders per manufacturer instructions. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items and storage within 3’ of equipment and piping.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |