Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed chlorine at 0.2 ppm at time of inspection. Maintain free chlorine at least 1.0 ppm chlorine. Operator added chlorine and corrected to 3.0 ppm. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Paramount SDX Retro cover on right side of pool not completely covering drain. Cover was secure, but not on center or installed correctly. Ensure drain covers are installed correctly and accordning to manufacturers instruction to avoid suction hazard.
**Issued Immediate Suspension for this item
Contact Marie Daley at 704-507-6806 when corrected to lift suspension |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool floor peeling near stairs. Keep in good repair. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Missing weir at time of inspection. Keep functional weir installed. Operator replaced. Corrected. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Inlet by life saving chair and stairs missing cover/fitting. Keep in good repair. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
One ring buoy starting to peel. On the second buoy the attachment piece starting to separate from buoy, which voids US Coast Gaurd Approved status. Must be in good repair. Replace. Operator is replacing immediately. (Rope should be 24' long) Will verify buoy condition when checking main drains. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restroom over 110 degrees F (117 degrees F). Maintain hot water at 110 degrees F or less. |