Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Incorrect pump information on submitted pdsc form. Corrected during inspection. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Observed rebar through wall on deep end of pool. Repair to eliminate hazard. Intent to Suspend issued.
Etching on pool floor. Keep in good repair. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Lane lines located within 5 ft of pool. Maintain 5 ft clearance around pool..
Damage to pool deck at flag post. Repair tiling. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Acid feeder does not turn off when pump turns off. Repair so that it detects flow and turns off. Intent to Suspend issued.
Flow meter located on line out of pump. Install on return line. |