7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Debris and leaves on pool floor. Main drains with some debris. Still visible. Keep pool floor clean. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Debris/leaves under skimmer baskets on two skimmers. Keep free of debris to ensure proper filtration of water through system. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Two windows (next to wall at treadmills and at far left of weight room) with window limiters >4"/not operable. Repair to limit windows at 4" or less. Intent to Suspend issued.
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Pool barrier at 44" at some pillars on wall. .2528(b) Horizontals shall not be located less than 45" in height. Barrier wall outside of pool fence located directly next to fence. <45" between horizontals from wall to fence and openings >4" above. Maintain 4" or less between openings. Pool built pre-2010. Observed mt gate at the back entry by the restrooms not permanently locked. Recommended to be locked when not used. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
.2524 For Night Swimming - provide sufficient lighting so that all parts of the pool and required deck area are visible and main drains are clearly visible.
One pool light not operational. Two lights to right of double doors (first and third light) not operational. Pool permitted for night swimming. Lights must be operable in pool and around perimeter for night swimming. Limit hours to dawn to dusk until repaired. Intent to Suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Floor wet due to leak at check valve. Repair leak or plumb catch drain to backwash pit to keep pump room floor dry.
Hose stored on floor next to pump in pump room. Maintain 3 ft. clearance around equipment in all locations. |