5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Expired testing reagents from 2021. Replace DPD-1, DPD-2, and pH reagent. Intent to Suspend issued. Cyanuric acid also running low but present and not expired. Recommend replacing also. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmers with debris in baskets. Keep skimmers free of debris to ensure operable filtration system. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Pool barrier at 44" at some pillars on wall. .2528(b) Horizontals shall not be located less than 45" in height. Barrier wall outside of pool fence located directly next to fence. <45" between horizontals from wall to fence and openings >4" above. Maintain 4" or less between openings. Pool built pre-2010. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
One light in pool burnt out and multiple perimeter lights burnt out. Pool seeking night swimming with previous approval where all lights were operable. Repair lighting. Pool not approved for night swimming until lighting is repaired. Intent to Suspend issued. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Incorrect phone number posted at emergency phone. Struck through and correct phone number. Off by one digit. Phone number shall match 911 and shall ring back to phone with dialed. Kings III phone tested and gave option to speak back through the phone. |