Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Pool barrier at 44" at some pillars on wall.
.2528(b) Horizontals shall not be located less than 45" in height. Barrier wall outside of pool fence located directly next to fence. <45" between horizontals from wall to fence and openings >4" above. Maintain 4" or less between openings. Observed cigarette waste receptacle next to barrier and <45" between top and top of barrier. Move to eliminate foothold.
Pool built pre-2010. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some damage to grout and tile around one skimmer. Offsets not >1/2". Continue to monitor and repair if worsens. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Check valve for fill line leaking. Provide catch drain to backwash pit to eliminate water on pump room floor. Could not verify ASSE listing on check valve. Placard worn off. Should be ASEE 1013.
Ventilation in door. Does not provide cross-ventilation. Provide continuous forced ventilation or cross ventilation. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Water in restrooms >110 F. Maintain at 110 F or below. |