| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 6.8. Maintain between 7.2 and 7.8. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records maintained daily; however, CPO stated that he was not recording daily. Records are the same every day. Assure accurate record keeping. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One skimmer without weir. Replace weir. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy grab rope starting to fray. Replace ring buoy and rope. Rope length required is 38 ft. Immediate Suspension issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Doors from concierge on to pool deck replaced with doors that do not self-close, self-latch. Repair to self-close, self-latch.
Cigarette container outside of fence provides foohold. Remove so not located directly next to fence.
3 1/2" under the gate/fence at entrances. Maintain 2" or less. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not operating. Only "1" is dialing. Repair phone so 911 can be contacted.
Phone number and address could not be read on labeling on phone. Relabel with address and phone number for phone.
Immediate Suspension issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Liquid automated chlorinator was off upon entrance to the pump room. Pool must be chlorinated by an NSF approved system. Pool to remain closed until return visit to verify chlorinator is operating properly.
Flow meter stuck. Keep operational. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No cross or forced ventilation in pump room. Provide.
Pump room floor wet due to leaking check valve. Keep pump room floor dry.
Acid stored directly in front of pump and valves. Maintain 3 ft clear walking distance around all equipment and valves. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Water in restrooms >110 F. Maintain at 110 F or below. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Check valve for fill line leaking. Clean out to eliminate leak. |