Water quality: pool water pH |
No |
No
|
No |
pH 7.1. .2535(1) Maintain pH at 7.2 to 7.8. Operator overshot to > 8.4. Acid feeder corrected it back to 7.6. Use acid demand test to determine correct amount of chemicals to add to the pool. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Most of February and part of January. pH consistently out of range, chlorine less than 1ppm with no corrective actions noted. Ensure chemicals are properly balanced daily. .2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir not attached to the skimmer. .2518(k) Provide functional weirs. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
One ring buoy with 23 foot throw rope. .2530(a) Provide USCG approved ring buoy with 18 foot throw rope. Corrected by operator. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Pre-2010 fence less than 48" high in places. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier.
Pre-20210 fence with gaps > 4" through the fence in places. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Spare pump basket not observed. .2518(e) Provide a spare basket for pump. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Major leak at the heater in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Fan in pump room not functioning. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Fan in chemical storage room not functioning. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restroom 127.5F. .2526(i) Water in restrooms shall not exceed 110 F. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drain in the restroom. .2526(c) Floor drains shall be provided in restrooms. |