5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Daily pool maintenance activities are not being recorded. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature. Provide weekly recordings for cyanuric acid and total alkalinity weekly. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir missing, other weir stuck. .2518(k) Maintain skimmers with functional weirs. Corrected by operator.
Skimmer baskets cracked. .2518(k) Replace missing or damaged skimmer basket. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Both throw ropes too long. .2530(a) Provide U.S. Coast Guard approved ring buoy for 18 foot throw rope. Corrected by operator. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Spare pump basket not observed. .2518(e) Provide a spare basket for pump. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan in chemcal storage room does not appear to be functioning. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Plastic bag of chemicals on chemical storage room floor. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Return lines and fill lines not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 110F. .2526(i) Water in restrooms shall not exceed 110 F. |