Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Daily records missing temperature of pool, but posted on wall.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
**30 Day Intent to Suspend (ITS) item. Will verify on return visit. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Distance between wall depth markers 0 FT to 2 FT exceeds 25' apart at time of inspection. No wall marker at 1 FT.
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool.
.2523(a) Provide depth markers on pool walls and pool deck next to the swimming pool.
**30 Day ITS item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Buoy rope observed at 60' at time of inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Required 50' at this pool. Operator cut to 50' and corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Multiple doors onto pool deck (from locker rooms and hallways) not self latching or alarmed at time of inspection .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
**30 Day ITS item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed water on pump room floor, not draining at time of inspection. Chemicals stored in pump room. Items within 3' of piping and equipment. Pump room for feature pumps not locking. Pool built 2002. .2533(d) Pump room floor shall be kept dry and free of standing water. .2533(d) Pump room floor shall be sloped to drain. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water over 110 degrees F in restrooms/locker rooms at time of inspection.
.2526(i) Water in restrooms shall not exceed 110 F. |