| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Water level 2 inches above the overflow trough. .2518(k) Water level shall be maintained such that overflow system is capable of providing continuous and automatic skimming action of the water at the surface of the pool. - Intent to suspend item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Some ladder handrails loose. Tighten and keep in good repair.
Some starting platforms are usable, pool open for general swim. .2517(e) Secure starting platforms from use by removal; covering; or signage and active supervision. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed doors to outdoor pool propped open. Corrected during inspection. .2537(b) All gates and doors shall be self-closing, self-latching.
Some doors not self-closing, or not self-latching. .2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Decking offset >1/2" at deck drain and deck near diving platforms. Offset is outside of required deck spacing.
Boards stored near one of the diving boards. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Inadequate indoor ventilation. Pool room hot. Doors propped open with large fans. Provide proper indoor ventilation. .2524(f) Indoor pools shall have mechanical ventilation. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Inadequate ventilation in chemical storage room where pallets of dry chemical is stored. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 120 F. .2526(i) Water in restrooms shall not exceed 110 F. |
|