| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Temperature not recorded daily. Maintain daily record keeping for temperature. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Damage to gutter near 17 ft at stairwell. Repair damage to gutter. Intent to Suspend issued. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Practice platforms without covering, signage or removal. Not in use at time of inspection. .2517(e) Secure starting platforms from use by removal; covering; or signage and active supervision.
One ladder handrail loose at deep end of pool. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One door nearest office not self-latching. Repair to self-close, self-latch. Intent to Suspend issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Practice equipment located directly behind large diving board. Maintain 5 ft. clearance behind any diving equipment.
Caps missing from holes in pool deck for equipment. Plugged during inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Equipment room outdoors without ceilings, walls, etc. Original construction.
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft.
Pump room area left unlocked. Keep locked when not in use. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Water in restrooms at exceeds 115 F. Maintain at 110 F or below. |
|