17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some minor chipping on deck. Monitor and repair if worsens or becomes a safety hazard. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. Original construction. If ever replaced, ensure flow meter installed per NSF requirement. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan in chemical storage room not operating. Repair fan per code requirements. Provide forced draw as required. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >116 F. Maintain at 110 F or below.
Loose toilet seat in the men's restroom. Keep fixtures in good repair. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Check valve for fill line ASSE 1015. Required ASSE 1013. Original construction. If ever replaced, replace with approved check valve. |