Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Operator was not aware that stabilizer was used in pool and was not recording cyanuric acid. Only one day kept and at least 100 ppm. Lower to below 100 ppm and maintain record keeping for CYA at least weekly. Intent to Suspend issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Painted deck beginning to chip near emergency phone. Continue to monitor and repair as needed. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Standing water on pump room floor. Keep free of standing water. Flooring shall be sloped to drain. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >110 F. Maintain at 110 F or below. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Check valve for fill line for pool rated ASSE 1015. Does not meet rule requirement. If ever replaced, replace with approved check valve.
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. |