Water quality: water temperature of heated pool |
No |
No
|
No |
Pool water 92.6 F at time of inspection. .2535(12) Maintain pool temperature at 90 F or below. Operator added water and lowered to 89.7 F. Corrected. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Weekly alkalinity missing on pool records. Unable to locate records for past month. Temperature recorded at 90 F with no corrections logged. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked and recorded. Corrected.
.2535(11) The pool operator must maintain records for at least six months. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
1 of 2 weirs missing at time of inspection. .2518(k) Replace missing weirs. Operator replaced. Corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Entry railing loose at time of inspection.
.2521 Install ladders per manufacturer instructions. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Becketts on buoy detached on 1 of 2 buoys on deck, voiding USCG approval. .2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Operator removed from deck and corrected.
Advised replacing both buoys prior to next inspection due to buoy starting to wear and becketts detaching. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operational at time of inspection.
.2518(g) Keep flow meter operational.
*Permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No 3' clearance around piping. Some water on floor in equipment room. Floor not sloped to drain. Pool built 2001. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(d) Pump room floor shall be sloped to drain.
.2533(d) Pump room floor shall be kept dry and free of standing water. |