5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drains not being checked correctly daily (operator thought drains indicated being backwashed). Educated operator on record keeping.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item. Will verify records on return visit |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Debris in skimmers at time of inspection. Operator cleaned and corrected.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
2 weirs missing. .2518(k) Replace missing weirs.
*Permit item |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder loose, not secure, deck starting to crack by ladder rail entry into deck at time of inspection.
.2521 Install ladders per manufacturer instructions. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some chairs and pool furniture within 6' of pool at time of inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times. Operator moved and corrected.
Deck cracking in 3 locations (two in coping, one crack by ladder).
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*Permit item |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Operator unable to locate spare pump basket at time of inspection. .2518(e) Provide a spare basket for pump.
*Permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No 3' clear walking space around piping. Dry chemicals stored on over vats of chemicals in chemical room. No backflow prevention on hose bibs. Lighting out in chemical storage. Water on floor in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(4) Provide storage for pool chemicals in waterproof containers, to prevent reaction or store up off the floor. .2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(b) Provide sufficient lighting in pump and chemical room.
.2533(d) Pump room floor shall be kept dry and free of standing water. |
|