2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm.
*Immediate Suspension item |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records missing maintenance when water out of compliance, inconsistent records with actual water quality.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Will check at return visit |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Feeder has been replaced with salt generator and not using tab feeder at time of inspection. Salt generation is not approved as primary chlorination.
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions.
*Permit item
Must use approved chlorinator for feeding to pool.
The reason tab feeder is no being used per CPO is because of high cyanuric acid levels for indoor pool. Pool using trichloro-s-triazinetrione. Reading label on tablets showed stabilizer in tablets. Discussed using appropriate chlorine tablets (unstabilized,no cyanuric acid) for indoor pool. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Water on floor in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(d) Pump room floor shall be kept dry and free of standing water. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms over 110 degrees F at time of inspection.
.2526(i) Water in restrooms shall not exceed 110 F. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drains in restrooms. Pool built 2000. .2526(c) Floor drains shall be provided in restrooms. |