Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameQUALITY SUITES
Address9840 PINEVILLE-MATTHEWS ROAD
 
City/State/ZIP
PINEVILLE NC 28134
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 10/10/2024
Final Score @ Grade
22
General CommentsImmediate suspension issued for chlorine and PDSC information. Correct items and contact Marie Daley at 704-507-6806 to lift suspension. Pool must remain closed with signage posted until suspension is lifted by Health department. Will verify weirs on return visit Submit PDSC to pdsc@mecknc.gov “E” Immediate suspension item

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. *Immediate Suspension item
6 6 Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ No No No Pump on file Hayward Superpump SP2605X7 3/4 pump in equipment room is Hayward W3SP2607X10, 1.1 HP. Submit updated PDSC form for approval. 2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. *Immediate suspension item
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Weir not installed. .2518(k) Provide functional weirs.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.