Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm.
*Immediate Suspension item |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Pump on file Hayward Superpump SP2605X7 3/4 pump in equipment room is Hayward W3SP2607X10, 1.1 HP. Submit updated PDSC form for approval. 2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
*Immediate suspension item |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Weir not installed. .2518(k) Provide functional weirs. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms over 110 degrees F at time of inspection.
.2526(i) Water in restrooms shall not exceed 110 F. |