2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm.
*Immediate Suspension item |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
PH 8.0 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8.
*Immediate Suspension item. |
|
4
|
6
|
Water quality: water temperature of heated pool |
No |
No
|
No |
Temperature of pool 99.5 F at time of inspection. .2535(12) Maintain pool temperature at 90 F or below.
*Immediate Suspension item |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No active certified pool operator (CPO) for establishment at time of inspection. Per a manger, there is a CPO, but is not on property daily. CPO should be responsible for training staff to ensure pool is maintained daily, including weekends and days CPO is absent. Records not being kept at time of inspection. .2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator..2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records
*30 Day Intent to Suspend (ITS) item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Unable to check back door at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
*Will check on return visit. *Permit item |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Feeder not working properly at time of inspection. Also unable to verify feeder shuts off with pump.
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions.
.2535 Automatic acid and chlorine feeders shall be automatically prevented from operating when the circulation pump is not in operation.
*30 Day ITS item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms over 110 degrees F at time of inspection.
.2526(i) Water in restrooms shall not exceed 110 F. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drains in restrooms. Pool built 2000. .2526(c) Floor drains shall be provided in restrooms. |