15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Buoy rope tangled and not long enough at time of inspection. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator untangled and corrected to 23'. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Phone number from 911 was 704-835-1421, not what was listed at emergency phone. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Operator corrected number on signage.
*Note: 911 called back and stated there was a hang up call when 911 was not dialed, but receiver picked up to test phone call back. Advised ensuring emergency phone only dials out for emergency calls. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. No backflow prevention on hose bib in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms over 110 degrees F at time of inspection.
.2526(i) Water in restrooms shall not exceed 110 F. |