NameCOUNTRY SUITES LAKE NORMAN
Address16617 STATESVILLE RD
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 2/17/2026
Final Score @ Grade
28
General CommentsInspection conducted with hotel manager Mike Kelaiya. No chemical safety placard on chemical storage room door. Recommend working with Fire Marshall to get correct chemical safety placard installed. Main drain covers expire 10-1-2026. Prior to expiration, replace with new APSP-16 approved covers and submit updated PDSC form to our office for approval. Immediate suspension issued 2) 23) Contact Will Harrison (704) 507-6824 for re-inspection when issues have been corrected.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No 0.1ppm free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Throw rope heavily knotted. .2530(a) Provide USCG approved ring buoy with attached 24 foot throw rope at least 1/4 inch in diameter. - Corrected.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Door to fitness room not always self-latching..2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Chlorine low, operator added tabs this morning. Manger turned chlorinator up, chlorine still very low at the end of the inspection. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Immediate suspension item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. Inadequate ventilation in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Some piping not labeled. No labeling on piping outside of the pump room. .2518(d) Piping and valves shall be labeled with color codes or labels.
27 2 Equipment room: filter backwash discharged through an air gap No No No Backwash not discharged through an air gap. .2513(b) Filter backwash shall be discharged through an air gap.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms 126.5F. .2526(i) Water in restrooms shall not exceed 110 F.