Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameCOUNTRY SUITES LAKE NORMAN
Address16617 STATESVILLE RD
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 11/13/2025
Final Score @ Grade
22
General CommentsInspection conducted with inspector Isaac Cathey and Komal Kelaiya. Inspection led by Isaac Cathey. Updated our records to reflect that Komal Kelaiya is the CPO for the pool. Permit restriction: flow meter must remain operable. Flow required at 48 GPM to 74 GPM to meet turnover and flow restriction of the filter. - Observed flow meter at 80 GPM. Flow meter appears to be installed to be accurate to within +/- 5%. Ensure that pump is operating within the required range. Emergency phone number calls back to front desk. Ensure someone is at the front desk whenever the pool is open. Observed sink drain slow in men’s restroom. Maintain sinks in good working order. Intent to suspend issued 5) 16)

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No main drain checks. Spotty total alkalinity and cyanuric acid checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item. Cyanuric acid consistently 100ppm in log book. Tested today at well over 100ppm. .2535 (4) Lower and maintain cyanuric acid at or below 100 ppm. - Intent to suspend item.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Ring buoy damaged. Throw rope heavily knotted. .2530(a) Provide USCG approved ring buoy with attached 24 foot throw rope at least 1/4 inch in diameter. - Corrected.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Door to fitness room not self-closing and self-latching..2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Some piping not labeled. No labeling on piping outside of the pump room. .2518(d) Piping and valves shall be labeled with color codes or labels.
27 2 Equipment room: filter backwash discharged through an air gap No No No Backwash not discharged through an air gap. .2513(b) Filter backwash shall be discharged through an air gap.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms 129.3F. .2526(i) Water in restrooms shall not exceed 110 F. Restroom stalls recently replaced. Both stalls in men’s restroom and one stall in women’s restroom do not have toilet paper dispensers. .2526(l) Provide toilet paper and dispensers in restrooms.