Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameCOUNTRY SUITES LAKE NORMAN
Address16617 STATESVILLE RD
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 8/12/2024
Final Score @ Grade
16
General CommentsInspection conducted with manager Mike Kelaiya. Items from previous inspection have been corrected. Permit issued. New Permit Condition: Flow meter must remain operable. Flow required at 48 GPM to 74 GPM to meet turnover and flow restriction of the filter. Paper permit will be on our website in 3-5 business days for your records.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No One weir missing. .2518(k) Replace missing weirs. Operator installed one of the weirs. - Corrected.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Door to fitness room not self-closing and self-latching..2537(b) All gates and doors shall be self-closing, self-latching. - Corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Fan was removed from the pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
27 2 Equipment room: filter backwash discharged through an air gap No No No Backwash not discharged through an air gap. .2513(b) Filter backwash shall be discharged through an air gap.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms > 110F. .2526(i) Water in restrooms shall not exceed 110 F.