6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Pool recently changed out pool pump. PDSC form not updated. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Immediate suspension item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Observed new US Coast Guard approved ring buoy and new throw rope. Rope too long and not attached. .2530(a) Provide USCG approved ring buoy with attached 24 foot throw rope. - Corrected. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not able to dial out. .2530(f) Emergency phone shall remain operable. - Immediate suspension item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Pool recently replastered. Eyeball fitting installed on vacuum line. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Intent to suspend item.
Spare pump basket not observed for new pump. .2518(e) Provide a spare basket for pump. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Fan was removed from the pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash not discharged through an air gap. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restroom 131.1F. .2526(i) Water in restrooms shall not exceed 110 F. |