Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No records since 11-5-2022. Cyanuric Acid tested consistently at 90 to 100 for last two months. Tested well over 100 ppm on today’s inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item.
Cyanuric acid tested more than 100 ppm. .2535 (4) Lower and maintain cyanuric acid at or below 100 ppm. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Missing both weirs. .2518(k) Replace missing weirs. Operator installed one of the weirs. - Intent to suspend item.
Skimmer basket damaged, bottom mostly broken off. .2518(k) Replace missing or damaged skimmer basket. - Intent to suspend item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Throw rope heavily knotted, and tied around the ring buoy. .2530(a) Provide USCG approved ring buoy with attached 24 foot throw rope. - Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door to fitness room standing open..2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some standing water on pool deck. .2522(f) Deck shall be sloped to drain. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in the pump room next to pool piping. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Inadequate ventilation in the pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Piping for heaters and fill lines not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash not discharged through an air gap. .2513(b) Filter backwash shall be discharged through an air gap. |