Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameCOUNTRY SUITES LAKE NORMAN
Address16617 STATESVILLE RD
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 2/2/2022
Final Score @ Grade
18
General CommentsInspection conducted with Paul Johnson. Due to COVID-19 precautions, inspection not signed by maintenance. Strong chlorine smell in pool area. Ensure ventilation system is working properly. Emergency phone number posted is for front desk phone. Ensure front desk is staffed whenever the pool is open or change so that 911 can call back directly to emergency phone on the pool deck. Immediate suspension issued 3) Contact Will Harrison (704-507-6824) for reinspection when issues have been corrected.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No pH 8.1. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Water level above the skimmers. .2518(k) Water level shall be maintained to assure skimmers are operable. - Intent to suspend item. Skimmers dirty, wads of hair. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Intent to suspend item.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladder loose. .2521 Install ladders per manufacturer instructions.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chemicals stored in the pump room next to pool piping. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Outdoor piping for heaters not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms 112.2F. .2526(i) Water in restrooms shall not exceed 110 F.