Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameCOUNTRY SUITES LAKE NORMAN
Address16617 STATESVILLE RD
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 1/19/2021
Final Score @ Grade
30
General CommentsInspection conducted with inspector Braeden Shelton and CPO Pierro Cominges. Due to COVID-19 precautions, inspection was not signed by the operator. Chemical storage room primarily used for general storage items. Recommend relocating or disposing of those items and use the chemical storage room to store pool chemicals. Chemical storage room not locked. Keep locked when not in use. Pool walls damaged, tiles broken. Maintain pool area in good condition. Water was murky on today's visit as well as some recent visits. May need to replace sand in the sand filter or use enzymes or other additives to help the filter and chlorine work more effectively. “Executive Order No. 141 or subsequent Orders are in effect unless such Orders are rescinded or superseded by another applicable Order.”

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No Cl 0.1ppm. .2535(4) Maintain chlorine at least 1.0 ppm. Corrected to 2 ppm.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No records since January 14th. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator arrived during inspection to check and correct chemicals.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Pool tiles dirty. Clean regularly. Paint chipping from pool floor. Repaint as needed. .2537(14) Maintain pool walls and floor in good condition.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Skimmers off the in pump room. Water about 3 inches low. .2518(k) Water level shall be maintained to assure skimmers are operable. Corrected by operator, added additional water.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Some chairs too close to pool edge. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chemicals stored in the pump room next to pool piping. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Pump room door doesn't close and lock. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. Pump room floor wet. Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Some of the piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
27 2 Equipment room: filter backwash discharged through an air gap No No No Backwash not discharged through an air gap. .2513(b) Filter backwash shall be discharged through an air gap.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms > 110F. .2526(i) Water in restrooms shall not exceed 110 F.