| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 0.3 ppm. Operator changed out chlorinator and after 30 minutes corrected to 0.5 ppm. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Pool using stabilized chlorine, no Cyanuric Acid checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item.
Chlorine checks consistently 3 - 5 ppm. Tested today at 0.3ppm. Ensure that test kit is accurate, samples taken away from returns, etc. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Paint on pool floor chipping off. Much worse than last inspection. Maintain pool walls and floor in good condition. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Missing one of two weirs. .2518(k) Replace missing weirs. - Intent to suspend item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder loose. .2521 Install ladders per manufacturer instructions. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. .2518(g) Keep flow meter operational. - Intent to suspend item.
Flow meter installed close to two elbows. .2518(g) Install flow meter on return line per manufacturer instructions. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals and non-chemical items all stacked on top of each other. Chemical storage room very cluttered. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Pump room door does not fully close, not able to stay locked. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Piping for heater not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 110F. .2526(i) Water in restrooms shall not exceed 110 F. |