| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records not being kept at time of visit. Last entry July 14, date of inspection Aug 2.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. Will check on return visit.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Some skimmers with debris at time of inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied baskets and corrected.
Multiple weirs missing.
.2518(k) Replace missing weirs.
*Permit item |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Top tread missing slip resistant strip on ladder.
.2521(b) Ladders shall have slip-resistant tread. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gap under fencing by grill area greater than 4”. Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010).
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Lighting fixture detached from pool wall, protruding causing hazard..2524(c) Lighting fixtures shall not present a hazard to the public.
*Permit item |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Inlet fitting missing at stairs and not circulating water. Fitting at bottom of pool by main drains missing. .2518(i) Arrange inlets to produce uniform circulation.
*Permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Equipment and chemicals stored under large plastic pieces outside. Dry bags of chemicals stored on floor under plastic rock with vats of liquid chemical. No walking space/clearance. Pump and chemicals not locked at time of inspection. Pool built '99.
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. |
|