Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 0 ppm at time of inspection.
.2535(4) Maintain chlorine at least 1.0 ppm. Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records not being kept on weekend at time of visit.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. Will check on return visit. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Chairs blocking body hook and buoy at time of inspection. Keep accessible.
.2530(a) Lifesaving equipment should be conveniently located. Operator moved chairs for accessibility and corrected.
Rope detached from buoy and not correct length.
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Operator reattached and cut to 35’. Corrected |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Chairs within 6' of pool and 5’ of handrails at time of inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times.
.2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. Operator moved and corrected. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Lighting fixture detached from pool wall, protruding causing hazard., .2524(c) Lighting fixtures shall not present a hazard to the public.
Will verify at return visit |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable at time of inspection. Flow restriction on pump must be at least 120 gpm for permit restriction. .2518(g) Keep flow meter operational.
Inlet fitting missing by stairs. .2518 Replace missing inlet fittings.
*Will verify at return visit |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Chemicals stored in garage with no ventilation. Pump not locked at time of inspection. Pool built '99.
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention device on spigot at shower. Provide backflow prevention device |