| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 0.2 ppm at time of inspection.
.2535(4) Maintain chlorine at least 1.0 ppm. Operator turned on chlorinator and corrected to 1.5 ppm. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid checks missing on records. No cyanuric acid reagent or test strip to test.
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Intent to Suspend (ITS) item |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Some skimmers with debris at time of inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied baskets and corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Bottom tread missing slip resistant strip on ladder.
.2521(b) Ladders shall have slip-resistant tread. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Chairs blocking body hook at time of inspection. Keep accessible.
.2530(a) Lifesaving equipment should be conveniently located. Operator moved chairs for accessibility and corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One gate not latching at time of inspection. .2537(b) All gates and doors shall be self-closing, self-latching. Operator adjusted to self-close, self-latch. Corrected.
Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010).
Landscaping shortening height of old fence by restroom entrance corner less than 48.
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Chemicals stored in garage with no ventilation. Pool built '99.
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Women's restroom out of order at time of inspection. No supplies at handsink and toilet out of order.
.2526(f) At least two sinks and two toilets required for women's restroom.
.2526(j) Provide soap and soap dispenser, no glass, at each sink.
.2526(m) Keep restrooms and fixtures clean and in good repair. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention device on spigot at shower. Provide backflow prevention device |