5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drain check not on records at time of inspection. Records missing daily records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added column for main drain check and corrected.
*Issued 30 Day Intent to Suspend (ITS) Will return to verify daily records |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Bottom tread missing slip resistant strip on ladder.
.2521(b) Ladders shall have slip-resistant tread. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Rope detached from buoy at time of inspection. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Operator tied rope onto buoy, secured and corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010).
Landscaping shortening height of fence by grill area less than 48.
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier.
*ITS item |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Chairs within 6' of pool at time of inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Water under pump. Chemicals stored in garage with no ventilation. Pool built '99.
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Dry chemicals in same area as liquid vats of acid and chlorine.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Operator moved dry chemicals. Corrected. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention device on spigot at shower. Provide backflow prevention device |