Water quality: pool water pH |
No |
No
|
No |
pH less than 6.8 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8.
**Immediate suspension item. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records in online system show entries for pool data days after due. Records inconsistent with observed pool water quality and drains on day of inspection (pH less than 6.8, records display 7.5, records indicate main drain checks, cover missing)
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records.
*Intent to Suspend item |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Skimmer equalizer cover missing at time of inspection. (Aquastar 8 HP, no longer manufacturered. Operator stated he would replace with 6 HP in mudring. Contact Katie Wilson or Chris Sells to discuss options for approval and replacement. .2537(7) Drain covers shall be in good condition and securely attached. Submit paperwork.
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
.2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used. **Immediate suspension item. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Variable speed set at 49 HZ at time of inspection. Permit restriction "Variable Speed Drive Set At 60 Hz" .2518(h) Provide approved pump in good repair.
Flow meter not operable at time of inspection. .2518(g) Keep flow meter operational.
**Intent to Suspend items |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention device on spigot at shower. Provide backflow prevention device |