6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Construction has been done. New pump installed (Pentair Whisperflo XFK-20 5HP) and piping, no paperwork available. Submit PDSC form and ensure no suction hazard exists. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir missing. Replace with functional weir. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One gate opens toward pool (appears to have been changed from opening outward). Gates should open away from pool. Stairs may be reason why this is installed this way. Will verify.
Construction was done, remvoing fencing and putting in brick wall 34" in height with gas lines creating footholds on end less than 45". Must maintain 48" in height from ground up/from footholds.
** 30 Day Intent to Suspend item |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency telephone not working at time of inspection. Construction is being done and has lines out.
**Immediate Suspension issued. Contact Marie Daley at 704-507-6806 when corrected to lift immediate suspension.
Pool closed signs posted. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not working at time of inspection. Install functioning flow meter.
No spare pump basket. Provide spare pump basket. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
New construction done and no labeling on pipes. Keep clearly identified with main drain, skimmer, vaccum lines and direction of flow. |