Water quality: water temperature of heated pool |
No |
No
|
No |
Water in pool over 90 degrees F at time of inspection.
.2535(12) Maintain pool temperature at 90 F or below. Heater turned off for correction and operator thermometer reading 89.8 degrees F. Corrected. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Pool built in '98. No spare pump basket. Unable to purchase/find. Provide spare pump basket. No permit action taken due to age of
pump and ability to find. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
3' clearance not provided around piping in pump room. Pool built prior to 2004.
.2533(c) Valves and controls shall be accessible to thepool operator at all times. Maintain 3 ft. clear walking space in pump room. Chemicals stored on floor in chemical room.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Piping with small leak at time of inspection. Keep in good repair. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water over 110 degrees F in showers at time of inspection.
.2526(i) Water in restrooms shall not exceed 110 F. |