2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Pool chlorine at 0 ppm. Maintain at 1.0 ppm through chlorinator. Facility had just switched to automated feeder. Immediate Suspension issued. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 6.9. Maintain at 7.2 to 7.8. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records not maintained as required. Maintain daily record keeping for chlorine, pH and main drain checks. Maintain weekly record keeping for cyanuric acid and total alkalinity. Permit Item.
Log book without area for main drain checks or cyanuric acid. Provide log book with all fields for record keeping. Permit Item.
Some reagents out of date. Replace reagents. Permit item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Two ladders loose. Ensure secure.
End caps missing off one ladder. Provide end caps. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door where log book is kept (middle door) sticking on concrete and not self-latching, self-closing. Repair to self-close, self-latch and so that door does not remain open when opened fully. Permit item. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Decking missing grout/seal in multiple locations within 6 ft. of pool. Repair decking to impervious surface within 6 ft. of pool. Requirement prior to 2022 operating permit. Notified on last inspection. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorinator without flow meter. Flow meter shall be installed in inlet line per NSF requirement. Original construction. New automated feeder installed. Verified feeder detects flow of pump during inspection. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib/floor drains in restrooms. Original construction. Provide hose bib with backflow prevention and floor drains. |