9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Observed depth markers on pool wall to be under the waterline and not be visable from certain vantage points. Post depth markers on the walls such that they denote the depth of the pool, in feet, in 4 inch high numbers every 25 feet around the edge of the pool. This alignment might be most easily accomplised by lining the wall markers up with the deck depth markers made of tiles. I.T.S. Issued. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Observed several eyeball fittings missing from the returns. Check all of the return fixtures and install proper fittings on the fixtures that are missing them. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Observed no body hooks on pool deck. 2 Body hooks are required as the pool surface is in excess of 3,000sqft. 2 Body hooks were obtained and placed on the deck. -C.D.I.
Observed ring buoy throw rope to be 55 feet long. The rope for this pool must be 50 feet long exactly. Rope was shortened to 50 feet in length. -C.D.I. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed ingress/egress doors not self-closing and self-latching. All ingress/egress doors must fully self-close and self-latch or be fitted with an audible alarm that alerts when the door is opened. This includes locker room doors leading onto the pool deck. I.T.S. Issued. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Observed Emergency Phone non-functional. New phone was installed and tested. -C.D.I. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Observed hot water in locker room sink to be 115F. Hot water in showers and sinks shall be no hotter than 110F. |