Premises Information

Return to Inspections
NameSLEEP INN
Address6300 BANNER ELK DR.
 
City/State/ZIP
CHARLOTTE NC 28216
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 11/13/2017
Final Score @ Grade
32
General CommentsIssued Immediate Suspension for #2, #3 and #4.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No Observed chlorine at 0.5ppm. Chlorine levels must be at at least 1.0ppm.
3 6 Water quality: pool water pH No No No Observed pH at 6.8. pH must be maintained between 7.2 and 7.8.
4 6 Water quality: water temperature of heated pool No No No Observed pool temperature at 94 degrees. Water temperature in pool should not exceed 90 degrees.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Observed daily maindrain recordings not being kept for November. Maintain daily, written record of main drain safety. Also keep weekly recordings of total alkalinity. No such records observed for November.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Observed peeling/chipping on pool floor and walls. Repair.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Observed deck chairs within 5ft of pools edge. Maintain 5ft of deck clearance at all points.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Observed boxes of tiles being stored in pumproom. Eliminate storage of non-pool items in pump room.