| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
No free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. - Corrected to 3ppm. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No recent total alkalinity, cyanuric acid, or maintenance activities. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pile of debris in the deep end of the pool. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Handrail loose. .2521 Install handrails per manufacturer instructions.
Both ladders loose. .2521 Install ladders per manufacturer instructions. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Chairs around handrail and in front of back door. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. - Intent to suspend item. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not functioning. .2530(f) Emergency phone shall remain operable and shall be capable of directly dialing 911 or another emergency notification system. - Corrected. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Vacuum off in the pump room. Observed vacuum cap not closed, spring damaged. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Difficult to access equipment due to low ceiling height. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Leak in the pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restroom 224F. .2526(i) Water in restrooms shall not exceed 110 F. |