3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH 8.0. .2535(1) Maintain pH at 7.2 to 7.8. Corrected to 7.7. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Both skimmer baskets cracked. Replace. .2518(k) Replace missing or damaged skimmer basket. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. .2518(g) Keep flow meter operational. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor wet. .2533(d) Pump room floor shall be kept dry and free of standing water.
Fan tied to light switch in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash line extends into the backwash pit. .2513(b) Filter backwash shall be discharged through an air gap. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Missing shower sign. .2526(a) Post a shower sign visible upon entrance to the pool. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restroom 123.2F .2526(i) Water in restrooms shall not exceed 110 F. |