Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One of the skimmers plugged with a water bottle. Maintenance forgot to remove it after vacuuming the pool. .2518(k) The flow-through rate through any one recessed automatic surface skimmer shall be between 20 gallons per minute and the maximum flow the skimmer is certified for under NSF Standard Number 50. Corrected. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
WARNING - NO LIFEGUARD ON DUTY signage missing WARNING and lettering less than 4" in height. .2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Metal float in flow meter installed upside down. .2518(g) Install flow meter on return line per manufacturer instructions. - Intent to suspend item. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash a direct connection. .2513(b) Filter backwash shall be discharged through an air gap. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Missing shower sign. .2526(a) Post a shower sign visible upon entrance to the pool. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 110F. .2526(i) Water in restrooms shall not exceed 110 F. |