3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH 6.9. Maintain between 7.2 and 7.8. Corrected to 7.3. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No recent Total Alkalinity records. No Cyanuric Acid records. Pool using stabilized chlorine. Check at least weekly Total Alkalinity and Cyanuric Acid. Maintain CYA at no more than 100ppm. - Intent to suspend item.
No records of pool maintenance activities. Record any maintenance activities such as chemical additions and filter backwash cyles. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Missing one weir. Install functional weir. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Back door not self-latching. Ensure door is self-closing and self-latching. - Intent to suspend item. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Underwater light does not work. Pool is open after dark. Provide sufficient lighting such that all parts of the pool floor are easily visible when operating. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. Repair or replace.
Provide spare pump basket for pool pump. None observed. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemical storage room fan tied to light switch. Provide either continuous forced air or cross ventilation in chemical storage room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Provide air gap for backwash. |