5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Récords missing daily maintenance. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator recorded and corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One ladder missing stair. .2521 Install ladders per manufacturer instructions. Operator replaced stair and corrected. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Buoy needing rope. Rope available.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator attached rope to buoy and cut to 30’ corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door onto pool deck not latching or alarmed at time of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Operator tightened and adjusted to self close, self latch. Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemical storage in pump room. Pool built 1990.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Toilets leaking in both restrooms.
.2526(m) Keep restrooms and fixtures clean and in good repair. |