11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder by 5' loose. Keep tight and in good repair. Ladder more than 6" from wall at bottom.
.2521 Install ladders per manufacturer instructions.
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Fence bolts have been removed creating gaps greater than 4" and fencing section able to be removed. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Operator bolted and secured to close gaps. Corrected.
Landscaping making fence height 44" in some sections. Pool built '90. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
No backflow prevention device on deck hose bib. .2522(h) Provide hose bibs with backflow prevention so that all arears of deck can be reached with a 100 ft hose. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Items around piping and equipment. Liquid chemicals over dry chemicals. Pool built '90.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Labeling faded on equipment piping at time of inspection. .2518(d) Piping and valves shall be labeled with color codes or labels. Operator labeled and corrected. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Discharge pipe has slit, but no air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap. |